LMC100
Sensor for point level detection
LMFCE-B12E-QSKG-0/US
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — LMC100-00 — 26.04.2021 —
Outputs
Total number of outputs
2
Output signal
switching signal; IO-Link
Electrical design
PNP/NPN
Number of digital outputs
2
Output function
normally open / normally closed; (parameterisable)
Max. voltage drop switching
output DC
[V]
2.5
Permanent current rating of
switching output DC
[mA]
50; (100 (...60 °C))
Short-circuit protection
yes
Type of short-circuit
protection
thermal, pulsed
Overload protection
yes
Measuring/setting range
Factory setting
water; hydrous media
Response times
Response time [s]
< 0.5
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SDCI standard
IEC 61131-9
Profiles
Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode
yes
Required master port type
A
Process data analogue
1
Process data binary
2
Min. process cycle time [ms]
2.3
Supported DeviceIDs
Type of operation DeviceID
Default 674
Operating conditions
Ambient temperature [°C]
-25...85
Storage temperature [°C]
-40...85
Protection
IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68)
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3 : closed tanks
DIN EN 61000-6-4 : open tanks
Shock resistance DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance DIN EN 60068-2-6 20 g (10...2000 Hz)
MTTF [years]
534
UL approval UL Approval no. H003